Both are listed, double-wall steel tanks. One is insulated so the fuel inside stays cool in a fire; the other relies on emergency venting, which has kept steel tanks from rupturing in fires since the lessons of the 1950s. Here is what each listing actually tests, what the codes require, and how to decide which one your site needs.
End views (cross-sections) of the three construction styles you will see quoted for fuel storage. Drawings are schematic, not to scale.
| UL 142 double wall | UL 142 + SwRI 97-04 (Flameshield, "fire resistant") | UL 2085 (Fireguard, "protected") | |
|---|---|---|---|
| What it is | Construction standard for shop-built steel aboveground tanks (first edition 1922; secondary containment added in the 1993 7th edition). | A double-wall UL 142 tank whose design passed a two-hour fire test under Southwest Research Institute's SwRI 97-04 program, administered by Steel Tank Institute. | A UL 142 primary tank with lightweight concrete (perlite) insulation and a steel outer wall, listed to UL 2085, Protected Aboveground Tanks. |
| Fire test | None for the assembly. Emergency vents are sized for fire exposure. | 2 hours in a 2,000°F hydrocarbon pool fire. Tank, supports and vents must hold; no leak afterward. | 2 hours in a 2,000°F hydrocarbon pool fire, plus a hose-stream test and post-fire leak test. |
| Inside temperature limit | Not tested. | No limit. The fuel boils off through the emergency vents, which carries the heat away. | Average rise no more than 260°F, no single point above 400°F (temperature rise of the primary tank). |
| Vehicle impact | Not part of the listing. Codes call for guard posts or barriers where vehicles can reach the tank. | Not part of the test. Guard posts or barriers per code. | Impact test included in the listing, marked on the label. |
| Ballistic (projectile) | Not tested. | Not tested. | Projectile test included in the listing. |
| Emergency venting | Required on the primary tank and on the interstice. | Required; proven to function during the fire test. | Required; the tested design may permit reduced vent capacity. |
| NFPA 30A setbacks at motor fuel dispensing (≤ 6,000 gal: property line / building / dispenser) | 100 ft / 50 ft / 50 ft | 50 ft / 25 ft / 25 ft (0 ft to dispensers at fleet sites) | 15 ft / 5 ft / 0 ft |
| Weight | Lightest. | Same as a UL 142 double wall. | Heaviest; the lightweight concrete adds substantial weight (concrete-encased designs far more). |
| SmartTank tank price, 1,000 / 3,000 / 8,000 / 12,000 gal | Flameshield: $5,973 / $13,907 / $34,800 / $45,560 | Fireguard: $18,855 / $35,385 / $65,620 / $85,635 | |
Setbacks: NFPA 30A (2018) Table 4.3.2.4, as summarized by Steel Tank Institute. Distances apply to motor fuel dispensing facilities under NFPA 30A; your adopted code edition and your AHJ govern. Prices are SmartTank's current tank-only prices from our AVGAS configurator (November 2026), before freight, equipment and installation.
NFPA 30 requires atmospheric aboveground tanks to be built to recognized engineering standards; UL 142, UL 2080 and UL 2085 all qualify. Its location tables (Table 22.4.1.1(a) and related tables) set distances to property lines and buildings, and allow shorter distances where there is protection for exposures: fire protection provided by a public fire department or private fire brigade able to cool the tank and nearby structures.
Section 4.3.2 recognizes protected (UL 2085), fire-resistant (UL 2080 or equivalent) and other NFPA 30 tanks at motor fuel dispensing facilities, up to 12,000 gal each (4.3.2.3), with the separation distances in Table 4.3.2.4. Protected tanks earn the shortest distances; that is their real advantage on a tight site.
NFPA 407 (2022) states that "fuel storage tanks shall conform to the applicable requirements of NFPA 30" (5.1.2.1), and leaves clearances from runways and taxiways to the authority having jurisdiction (5.1.2.2). The standard does not call for protected or UL 2085 tanks at airports, including for self-service fueling (8.1.2).
For aboveground tanks at motor fuel-dispensing facilities, the IFC calls for UL 2085 tanks for Class I liquids, and allows other tank types for Class II and IIIA liquids with the fire code official's approval. It does not recognize the fire-resistant category. Where a state has adopted the IFC, check whether the airport fuel farm falls under this section or under the general tank provisions of Chapter 57.
Codes give the authority having jurisdiction room to judge the actual risk at the site. Questions worth putting in front of yours:
A tank in a fire fails when vapor pressure builds faster than it can escape. Emergency vents, sized to the tank's wetted surface area, let the boiling fuel vent its vapor at low pressure. Boiling is what protects the tank: as long as fuel is boiling against the shell, the energy from the fire goes into vaporizing fuel instead of heating the steel past its strength.
Insulation works differently. In a UL 2085 tank the insulation keeps the fuel from boiling in the first place, so less vapor is produced. Both approaches end the same way: neither a properly vented double-wall tank nor an insulated tank ruptures. The difference is how hot the fuel gets, and gasoline and avgas autoignition temperatures sit well above 800°F, far beyond what a vented tank's contents reach while boiling.
We are not aware of a listed UL 142 tank with properly sized emergency vents rupturing in a fire.
We build and sell both. A UL 2085 tank is the right call where the code or the fire marshal requires it, or where a tight site needs the short setbacks. For most airports, where the tank sits on open ground away from buildings, fire protection is close by and the people fueling are trained pilots, a double-wall UL 142 tank with proper emergency venting, Flameshield fire testing and guard posts protects life safety just as well, for a fraction of the cost. NFPA 407 does not require more.
Ask your fire marshal early, bring the site plan, and let us help you make the case.
Price both in the AVGAS configuratorWe'll help you choose the tank and make the case to your fire marshal.